These steps below explain the disk addressing and cabling for the D1000 only.



CABLING THE D1000



The D1000 68 pin connect is Differential Ultra SCSI connections.



The D1000 is available in 2 models, a 8 drive or 12 drive system.



The D1000 has the capitablity of using all 8 or 12 drives on one

host.  Or you can divide your D1000 into 2 backplanes each using

4 or 6 drives, depending on which model you have, on each host. 

The D1000 CAN NOT be dual hosted.





On the rear of the D1000 you have 4 68pin scsi connectors.



If you will be connecting all 8 or 12 drives to one system you will

need to connect the scsi cable from the host to the far left

or the far right connector.  On the other far right or left

68pin connection you need to connect a differential terminator 

(Part Number 150-1890).  The 2 inside connections you will need

to connect to each other using the small scsi cable which

came with the D1000 (Part number 530-1883).



If you will be using the D1000 as 2 backplanes of 4 or 6 drives each, you 

will need to connect HOST-A to the far left 68pin connector.  Then connect 

HOST-B to the far right 68pin connector. Then the 2 inside 68pin connectors

each need to have a differential terminator (part number 150-1890) connected.



SETTING TARGET ADDRESS



You can change the address of the drives by changing the dipswitch settings

on SW1.





SWITCH	DIP	SETTING		DESCRIPTION

------  ---     -------         -----------

  SW1    1        UP*	Addresses 4 right drives to 8 - 11 or 8 - 13

  SW1    1       DOWN   Addresses 4 right  drives to 0 - 3 or 0 - 5

  SW1    2        UP    Addresses 4 left drives to 8 - 11 or 8 - 13 

  SW1    2       DOWN*  Addresses 4 left  drives to 0 - 3 or 0 - 5

  SW1    3        UP    Wait for a start unit command

  SW1    3       DOWN*  Uses the SW1 dip 4 settings 

  SW1    4        UP*   Delay each drive 12 sec X the drive id

  SW1    4       DOWN   Start all drives on power on

  SW1    5      UP/DOWN Reserved for future use on the D1000

  



* denotes default settings.



NOTE:  You must be careful in setting the switches.  If you are not carefull

       you can have conflict in the target address when using all drives

       on a single host.  







REFERENCE MATERIAL



Sun StorEdge A1000 & D1000 Installation, Operation & service manual

p/n 805-2624            